Notifications
You must be signed in to change notification settings - Fork 57
New issue
Have a question about this project? # for a free GitHub account to open an issue and contact its maintainers and the community.
By clicking “#”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.
Already on GitHub? # to your account
BK1120 BusCoupler with K-Bus terminals #69
Comments
I am not sure if that is the problem. According to the spec, if SDO Upload happens with "Complete Access" mode, and sub index 0 is requested, it will be padded to 16 bits. Can you see from within Wireshark if the the "Complete Access"-bit is set? From your log I cannot check it. EtherCAT.NET/native/SOEM_wrapper/soem_wrapper.c Lines 1013 to 1027 in 51f59a8
Does it work with pure SOEM code? What helped me often is to compare the TwinCAT Wireshark log to the SOEM/EtherCAT.NET Wireshark log. It is helpful then to reduce the number of connected slaves to a minimum because TwinCAT executes multiple commands per frame which makes searching the Wireshark log more difficult. |
Ok, said bit is set. What is the consequence for the format of the 'dataset' variable. Does it depend on the byte order HighByte/LowByte (Endian)? EtherCAT Mailbox Protocol:CoE SDO Req : 'Initiate Download' (1) Idx=0x427f Sub=0 |
The dataset variable should not be changed. The padding is an implementation detail. But the set "complete access" bit is a hint that the data is transmitted correctly. What I would do now is to compare TwinCAT and SOEM/EtherCAT.NET Wireshark logs. |
I had no TwinCAT setup on my machine on hand. But I tested the unit with the "Simple_Test"-code which worked fine. When than compared with the WireShark-log below I found that there are some added bytes in the CoE-section. The field 'length' does not appear in the 'Simple_Test' log. The consequence is, that after the subIndex byte (00) a sequence of 4 bytes follows were only 2 bytes are expected. Since I have no idea how to control this value it remains random and therefor a undefined address is used. The data in the said field is the order of the connected terminals. EtherCAT Mailbox Protocol:CoE SDO Req : 'Initiate Download' (1) Idx=0x427f Sub=0 0000 ff ff ff ff ff ff 03 01 01 01 01 01 88 a4 94 10 ................ |
may be I misunderstood the protocol. It seems do be right. However, I don't see that the load data are more than 4 Byte which according to the specs should result in an additional field of the protocol. Actually they are only 2 Bytes long: 0x0005. |
Hello,
I' am experimenting with the SOEM code since a while. I still have no success in get the thing running. It always throws an exception saying: 'SdoWrite failed <0x0000>: The working counter is 0 '
The exception is thrown when trying ' master.Configure(rootSlave); '
It seems, that the type of dataset does not match. The WireShark log shows a value of 500 but should be 5.
Is there any workaround for this problem?
`
`
WireShark response.
`No. Time Source Destination Protocol Length Info
157042 0.000258 03:01:01:01:01:01 Broadcast ECAT 164 'FPWR': Len: 136, Adp 0x1001, Ado 0x1c00, Wc 1 Mbx(CoE SDO Req : 'Initiate Download' (1) Idx=0x427f Sub=0)
Frame 157042: 164 bytes on wire (1312 bits), 164 bytes captured (1312 bits)
Ethernet II, Src: 03:01:01:01:01:01 (03:01:01:01:01:01), Dst: Broadcast (ff:ff:ff:ff:ff:ff)
EtherCAT frame header
EtherCAT datagram(s): 'FPWR': Len: 136, Adp 0x1001, Ado 0x1c00, Wc 1
EtherCAT datagram: Cmd: 'FPWR' (5), Len: 136, Adp 0x1001, Ado 0x1c00, Cnt 1
Header
EtherCAT Mailbox Protocol:CoE SDO Req : 'Initiate Download' (1) Idx=0x427f Sub=0
Header
CoE
Number: 0
Type: SDO Req (2)
SDO Req : 'Initiate Download' (1) Idx=0x427f Sub=0
Index: 0x427f
SubIndex: 0x00
Length: 0x00000002
Data: 0500
Data: 000000000000000000000000000000000000000000000000000000000000000000000000…
Data: 000000000000000000000000000000000000000000000000000000000000000000000000…
Working Cnt: 1
Working Cnt: 1
WireShark.txt
`
The text was updated successfully, but these errors were encountered: