skyspark-simultaneous-cool-and-heat

SkySpark: Extension demonstrating testing of Axon-based function to detect simultaneous cooling and heating

The extension provides an Axon function simultaneousCoolAndHeat(), which detects whether heating and cooling is occurring simultaneously on, say, an AHU. (It's very similar in functionality to ahuCoolAndHeat() in the HVAC module).

More importantly, this extension contains Fantom-based code to test simultaneousCoolAndHeat(). After compilation, the tests may be run with the command:

fant simultaneousCoolAndHeatExt

And you should see the lovely text:

All tests passed! [1 tests, 6 methods, 19 verifies]

However there is a second feature in the extension, the ability to check the configuration of records. This feature is provided by the Axon function simultaneousCoolAndHeatTestModel(). This function either returns null on success, or a string describing any problems that were detected. For example, the following can be executed from within the Folio app in the Demo Project:

// returns null to indicate success
simultaneousCoolAndHeatTestModel(@Headquarters.AHU-1)

// returns "The equipment's cool points aren't correctly configured.
// There is not at least one match for the filter cool and point and
// equipRef==@Headquarters.ElecMeter-Main and his and tz and kind."
simultaneousCoolAndHeatTestModel(@Headquarters.ElecMeter-Main)