fix(hvac): Better defaults for DOAS vs. All-air and Chiller COP
Browse files Browse the repository at this point in the history
  • Loading branch information
chriswmackey authored and Chris Mackey committed Oct 11, 2022
1 parent 97f11dc commit 84cb663
Showing 1 changed file with 21 additions and 12 deletions.
33 changes: 21 additions & 12 deletions lib/to_openstudio/hvac/template.rb
Original file line number Diff line number Diff line change
Expand Up @@ -115,50 +115,59 @@ def to_openstudio(openstudio_model, room_ids)
end
end

# set the efficiencies of supply components in the air loop
# set the efficiencies of fans to be reasonable for DOAS vs. All-Air loops
if !os_air_loops.empty?
if equipment_type.to_s.include? 'DOAS'
fan_size = 0.2
else
fan_size = 2
end
os_air_loops.each do |os_air_loop|
# set the supply fan efficiency
unless os_air_loop.supplyFan.empty?
s_fan = os_air_loop.supplyFan.get
s_fan = fan_from_component(s_fan)
unless s_fan.nil?
s_fan.setMaximumFlowRate(1)
s_fan.setMaximumFlowRate(fan_size) # set to a typical value
standard.fan_apply_standard_minimum_motor_efficiency(
s_fan, standard.fan_brake_horsepower(s_fan))
s_fan.autosizeMaximumFlowRate()
s_fan.autosizeMaximumFlowRate() # set it back to autosize
end
end
# set the return fan efficiency
unless os_air_loop.returnFan.empty?
ex_fan = os_air_loop.returnFan.get
ex_fan = fan_from_component(ex_fan)
unless ex_fan.nil?
ex_fan.setMaximumFlowRate(1)
ex_fan.setMaximumFlowRate(fan_size) # set to a typical value
standard.fan_apply_standard_minimum_motor_efficiency(
ex_fan, standard.fan_brake_horsepower(ex_fan))
ex_fan.autosizeMaximumFlowRate()
ex_fan.autosizeMaximumFlowRate() # set it back to autosize
end
end
end
end

# get the boilers and assign the correct efficiency
# get the boilers and assign a reasonable efficiency (assuming 40kW boilers)
if equipment_type.to_s.include? 'Boiler'
openstudio_model.getBoilerHotWaters.sort.each do |obj|
obj.setNominalCapacity(40000) # set to a dummy value for the method
obj.setNominalCapacity(40000) # set to a typical value
standard.boiler_hot_water_apply_efficiency_and_curves(obj)
obj.autosizeNominalCapacity() # set it back to autosize
obj.setName(standard_id + ' Boiler')
end
end

# get the chillers and assign a reasonable COP from the standard
# get the chillers and assign a reasonable COP (assuming 2000kW water-cooled; 600kW air-cooled)
if equipment_type.to_s.include? 'Chiller'
# set the chiller efficiency
if equipment_type.to_s.include? 'ACChiller'
chiller_size = 600000
else
chiller_size = 2000000
end
clg_tower_objs = openstudio_model.getCoolingTowerSingleSpeeds
openstudio_model.getChillerElectricEIRs.sort.each do |obj|
obj.setReferenceCapacity(2000000) # set to a dummy value for method
obj.setReferenceCapacity(chiller_size) # set to a typical value
if obj.name.empty?
obj_name = standard_id + ' Chiller'
else
Expand All @@ -170,7 +179,7 @@ def to_openstudio(openstudio_model, room_ids)
end
end

# set the efficiency of any gas heaters
# set the efficiency of any gas heaters (assuming 10kW heaters)
if equipment_type.to_s.include? 'GasHeaters'
zones.each do |zon|
zon.equipment.each do |equp|
Expand All @@ -179,7 +188,7 @@ def to_openstudio(openstudio_model, room_ids)
coil = unit_heater.heatingCoil
unless coil.to_CoilHeatingGas.empty?
coil = coil.to_CoilHeatingGas.get
coil.setNominalCapacity(10000) # set to a dummy value for method
coil.setNominalCapacity(10000) # set to a typical value
standard.coil_heating_gas_apply_efficiency_and_curves(coil)
coil.autosizeNominalCapacity() # set it back to autosize
end
Expand Down

0 comments on commit 84cb663